Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 Condition Monitoring Unit CMU 1000 User manual (Translation of original manual)
Condition Monitoring Unit CMU 1000 Page 10 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 Danger! means that death, severe bodily injur
Condition Monitoring Unit CMU 1000 Page 100 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.7 Boolean Links 7.7.1 Not The Not funct
Condition Monitoring Unit CMU 1000 Page 101 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.7.4 Or The Or function links the two Bool
Condition Monitoring Unit CMU 1000 Page 102 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.7.6 Exclusive Or The Exclusive Or functio
Condition Monitoring Unit CMU 1000 Page 103 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.8 Other Boolean Operations 7.8.1 Note Va
Condition Monitoring Unit CMU 1000 Page 104 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.8.3 T - Flipflop The T-FlipFlop functio
Condition Monitoring Unit CMU 1000 Page 105 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.8.5 RS - Flipflop The RS-FlipFlop functi
Condition Monitoring Unit CMU 1000 Page 106 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.9 Result Values 7.9.1 Numerical Output Va
Condition Monitoring Unit CMU 1000 Page 107 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.9.2 Boolean Output Value The Boolean ou
Condition Monitoring Unit CMU 1000 Page 108 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.10 Actions 7.10.1 Setting Switching Outp
Condition Monitoring Unit CMU 1000 Page 109 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.10.3 Display Message The Display message
Condition Monitoring Unit CMU 1000 Page 11 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 2 Safety 2.1 General Safety Precautions Foll
Condition Monitoring Unit CMU 1000 Page 110 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.10.5 Compiling a Log Entry The Compile
Condition Monitoring Unit CMU 1000 Page 111 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.10.9 Send SMS The Send SMS function is u
Condition Monitoring Unit CMU 1000 Page 112 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 8 Error Messages CM Program Compilation In
Condition Monitoring Unit CMU 1000 Page 113 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 8.1 Overriding Error Messages 8.1.1 Functi
Condition Monitoring Unit CMU 1000 Page 114 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 8.2.9 No Inscription with Numerical Input T
Condition Monitoring Unit CMU 1000 Page 115 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 8.4.3 Invalid Digital Output The quantity o
Condition Monitoring Unit CMU 1000 Page 116 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 8.4.12 Message and Telephone Number too Lon
Condition Monitoring Unit CMU 1000 Page 117 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 9 Technical Data 9.1 Power Supply - Input
Condition Monitoring Unit CMU 1000 Page 118 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 9.6 Analog Outputs Quantity: 2 Type:
Condition Monitoring Unit CMU 1000 Page 119 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 9.9.5 Serial Interface 0 (UART 0) The seria
Condition Monitoring Unit CMU 1000 Page 12 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 2.2 Proper/Designated Use The CMU1000 is an e
Condition Monitoring Unit CMU 1000 Page 120 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 9.14 Scope of Delivery The CMU 1000 is pack
Condition Monitoring Unit CMU 1000 Page 121 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 11 Accessories • SMART Sensors HLB 1000 - Se
Condition Monitoring Unit CMU 1000 Page 122 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 HYDAC ELECTRONIC GMBH Hauptstraße 27 D-6612
Condition Monitoring Unit CMU 1000 Page 13 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 3 Setup and Function The CMU1000 is an elect
Condition Monitoring Unit CMU 1000 Page 14 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 3.3 Terminal Allocations Plugs Pin Channel
Condition Monitoring Unit CMU 1000 Page 15 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 Plugs Pin Channel Function I/O 1 C
Condition Monitoring Unit CMU 1000 Page 16 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 AS 1000 +UB GND HSI 1 2 3
Condition Monitoring Unit CMU 1000 Page 17 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 3.4.2 Standard HSI Sensors 3.4.3 Standard
Condition Monitoring Unit CMU 1000 Page 18 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 3.4.5 GSM Module CSI-F-10 1 HSI Master
Condition Monitoring Unit CMU 1000 Page 19 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 min. 25 mm min. 25 mm 4 Installation and Ini
Condition Monitoring Unit CMU 1000 Page 2 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749
Condition Monitoring Unit CMU 1000 Page 20 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 4.2 Control Element on the Device The follow
Condition Monitoring Unit CMU 1000 Page 21 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 4.4 Behavior when Switching On/Restart The C
Condition Monitoring Unit CMU 1000 Page 22 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 If one or more output values are programmed i
Condition Monitoring Unit CMU 1000 Page 23 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5 Basic Settings/Menu Structure The CMU 1000
Condition Monitoring Unit CMU 1000 Page 24 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 Level 1 Level 2 Level 3 Level 4 Level 5
Condition Monitoring Unit CMU 1000 Page 25 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2 Configuration Using CMWIN PC Software Th
Condition Monitoring Unit CMU 1000 Page 26 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • Mark the option "Direct Connection&qu
Condition Monitoring Unit CMU 1000 Page 27 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • In the Interface field, select the option
Condition Monitoring Unit CMU 1000 Page 28 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • Pressing "Disconnect" in the Dev
Condition Monitoring Unit CMU 1000 Page 29 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.2 Direct Connection via HSI Bus You can
Condition Monitoring Unit CMU 1000 Page 3 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 Table of Contents 1 General...
Condition Monitoring Unit CMU 1000 Page 30 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.2.2 Connection Setup via CSI-B-2 Interfa
Condition Monitoring Unit CMU 1000 Page 31 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • Select Change in the Bus address line. Th
Condition Monitoring Unit CMU 1000 Page 32 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.2.3 Device Connection without CSI-B-2 In
Condition Monitoring Unit CMU 1000 Page 33 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • If the Connection window does not open aut
Condition Monitoring Unit CMU 1000 Page 34 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • To set up a connection with one "Slav
Condition Monitoring Unit CMU 1000 Page 35 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • Select Change in the Bus address line. Th
Condition Monitoring Unit CMU 1000 Page 36 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • The following message now appears in the M
Condition Monitoring Unit CMU 1000 Page 37 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.3 Modem Connection You also have the opti
Condition Monitoring Unit CMU 1000 Page 38 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.3.2 Establishing Connection with GSM Rad
Condition Monitoring Unit CMU 1000 Page 39 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • The following message appears: • Selec
Condition Monitoring Unit CMU 1000 Page 4 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.3 Modem Connection...
Condition Monitoring Unit CMU 1000 Page 40 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • Successful establishment of the connectio
Condition Monitoring Unit CMU 1000 Page 41 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • Click on "Disconnect" under Conn
Condition Monitoring Unit CMU 1000 Page 42 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.3.3 Connection Setup with CMU 1000 using
Condition Monitoring Unit CMU 1000 Page 43 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • You can set up a list of telephone numbers
Condition Monitoring Unit CMU 1000 Page 44 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • The following message appears: • Confirm
Condition Monitoring Unit CMU 1000 Page 45 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.4 TCP Connection As a third option, you c
Condition Monitoring Unit CMU 1000 Page 46 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • Enter the IP Address stored in the networ
Condition Monitoring Unit CMU 1000 Page 47 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • End the connection setup by confirming w
Condition Monitoring Unit CMU 1000 Page 48 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.5 Actions 5.2.5.1 Display Device Status
Condition Monitoring Unit CMU 1000 Page 49 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.5.2 Display Device Information • Here t
Condition Monitoring Unit CMU 1000 Page 5 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.2 Data Sources ...
Condition Monitoring Unit CMU 1000 Page 50 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.5.4 Managing Recordings • Here you can m
Condition Monitoring Unit CMU 1000 Page 51 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 Recording settings Here you specify whether
Condition Monitoring Unit CMU 1000 Page 52 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 Network settings If the CMU 1000 is integrat
Condition Monitoring Unit CMU 1000 Page 53 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • Channel I to Channel P - Name [Enter na
Condition Monitoring Unit CMU 1000 Page 54 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • PWM 1, PWM 2 (Analog output 1, Analog ou
Condition Monitoring Unit CMU 1000 Page 55 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.5.6 Managing Configurations Here you can
Condition Monitoring Unit CMU 1000 Page 56 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 - With Load you can transfer a configuration
Condition Monitoring Unit CMU 1000 Page 57 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • Settings The basic settings and the networ
Condition Monitoring Unit CMU 1000 Page 58 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • Input configuration The values of the nume
Condition Monitoring Unit CMU 1000 Page 59 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.5.8 Managing Sensor Constellations Relia
Condition Monitoring Unit CMU 1000 Page 6 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.6.7 Within...
Condition Monitoring Unit CMU 1000 Page 60 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.5.9 Display Input Values • Here the cur
Condition Monitoring Unit CMU 1000 Page 61 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.6 Extras 5.2.6.1 Update Firmware Caution
Condition Monitoring Unit CMU 1000 Page 62 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • Confirming with Continue will cause the da
Condition Monitoring Unit CMU 1000 Page 63 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • Confirming again with Continue will activ
Condition Monitoring Unit CMU 1000 Page 64 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.6.2 Set Password Protection • To preven
Condition Monitoring Unit CMU 1000 Page 65 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 5.2.6.3 Change Password • Here you have the
Condition Monitoring Unit CMU 1000 Page 66 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 6 CM Editor The CMU 1000 processes your progr
Condition Monitoring Unit CMU 1000 Page 67 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 6.1 Menu Bar The menu bar of the CM Editor is
Condition Monitoring Unit CMU 1000 Page 68 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 6.1.2 CM Program • After "Display"
Condition Monitoring Unit CMU 1000 Page 69 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 With "Perform cycle", you can sta
Condition Monitoring Unit CMU 1000 Page 7 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 8.3.3 Lower Measured Value Limit Greater than
Condition Monitoring Unit CMU 1000 Page 70 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • You can transfer the currently opened CM p
Condition Monitoring Unit CMU 1000 Page 71 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • You can transfer and then edit the CM prog
Condition Monitoring Unit CMU 1000 Page 72 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 6.1.3 Grouping • With Create grouping you ca
Condition Monitoring Unit CMU 1000 Page 73 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 6.1.5 Sensor Constellation Reliable system mo
Condition Monitoring Unit CMU 1000 Page 74 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • With Uninstall you delete the currently av
Condition Monitoring Unit CMU 1000 Page 75 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 6.1.6 Sensor Configuration Sensor configurati
Condition Monitoring Unit CMU 1000 Page 76 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 • When the Display function is selected, a w
Condition Monitoring Unit CMU 1000 Page 77 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 6.1.7 Extras • The following window opens wi
Condition Monitoring Unit CMU 1000 Page 78 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 6.2 Window Divisions The graphics interface o
Condition Monitoring Unit CMU 1000 Page 79 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7 CM Program Functions A CM program consists
Condition Monitoring Unit CMU 1000 Page 8 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 Preface We have compiled the most important
Condition Monitoring Unit CMU 1000 Page 80 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.1.2 Parameters Parameters are defined in th
Condition Monitoring Unit CMU 1000 Page 81 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.2 Data Sources 7.2.1 Numerical Constant T
Condition Monitoring Unit CMU 1000 Page 82 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.2.4 Numerical Entry The function Numerical
Condition Monitoring Unit CMU 1000 Page 83 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.2.6 Time Sensor The Time sensor is a func
Condition Monitoring Unit CMU 1000 Page 84 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.2.8 Error Event An error handling can be i
Condition Monitoring Unit CMU 1000 Page 85 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 Additional points for sequency controls in th
Condition Monitoring Unit CMU 1000 Page 86 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.3 Numerical Calculations 7.3.1 Addition T
Condition Monitoring Unit CMU 1000 Page 87 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.3.5 Division Remainder The Division remain
Condition Monitoring Unit CMU 1000 Page 88 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.3.9 Raising to a Higher Power The Raisin
Condition Monitoring Unit CMU 1000 Page 89 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.3.13 Decade Logarithm The Decade logarithm
Condition Monitoring Unit CMU 1000 Page 9 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 1 General This manual is a constituent part of
Condition Monitoring Unit CMU 1000 Page 90 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.3.15 Differential Quotient The Differentia
Condition Monitoring Unit CMU 1000 Page 91 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.4 Numerical Operations 7.4.1 Minimum The
Condition Monitoring Unit CMU 1000 Page 92 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.4.5 Median Value The Median value funtion
Condition Monitoring Unit CMU 1000 Page 93 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.4.8 Note Maximum The Note maximum function
Condition Monitoring Unit CMU 1000 Page 94 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.4.10 Tabular Index The Tabular index func
Condition Monitoring Unit CMU 1000 Page 95 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.4.12 Slope The Slope function is used to
Condition Monitoring Unit CMU 1000 Page 96 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.5 Counting Functions 7.5.1 Count Pulses T
Condition Monitoring Unit CMU 1000 Page 97 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.6 Numerical Conditions 7.6.1 Equals The
Condition Monitoring Unit CMU 1000 Page 98 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.6.3 Greater than The Greater than function
Condition Monitoring Unit CMU 1000 Page 99 Revised 17.12.2009 HYDAC ELECTRONIC GMBH Mat.-No.: 669749 7.6.6 Less than or Equal to The Less than